Measurement of ground resistance with earth ohmeter
Principle of operation of earth ohmeter
![]() |
If it parts 5-10m or more in radius from the earth point, the method of
measuring the ground resistance with an earth ohmeter on the market uses the
thing with a little influence of the current with the earth. It is an earth that E starts measuring by the measuring method of a left ground resistance. Supplementary earth stick P is driven in a point 5-10m or more away from this earth and supplementary earth stick C is driven to a point 5-10m or more on the same extension line away in addition. Current I is thrown applying exchange voltage V between E and C. Re, Rp, and Rc are the ground resistance in each earth pole. Voltage Ve between earth pole E and P is measured with AC voltmeter M. Because the current doesn't flow to Rp at this time, this resistance is irrelevant. Ve = I*Re Re = Ve/I It becomes it. It is possible to measure it actually only by reading the numerical value of the earth ohmeter even if such a calculation is not done. If it is not a point that the voltage doesn't change even if P point moves the place in the place a little by the potential of the earth in the voltage distribution of left figure, an accurate measurement cannot be done. The reason for the extent of the impact of the ground resistance of Re and Rc because is that it is about 5-10m or more ..the earth point... Separating the supplementary earth stick more greatly than the earth point becomes important when the resistivity of the soil is large. |
Measurement of ground resistance with earth ohmeter
![]() |
This photograph is a transistor type automatic operation earth ohmeter of
PDR-100 analog of Sanwa. The earth resistance measurement method is three
electrode method or two electrode method of the fixed current method.
Three electrode method is a measuring method by the above-mentioned theory. The leftmost terminal E of a left photograph is connected with the earth that measures the ground resistance. There are terminal P and terminal C for the supplementary earth pole in the right. Two electrode method is short-circuited of the terminal of C and P so that an already-known earth is near by the measuring method at being, measures the resistance between terminals E by the ground resistance, and subtracts already-known earth resistance. An accurate measurement is possible, and it still uses it for the theory in the active service because it faithfully measures it though it is an old earth ohmeter. The range of 0-1k Ohm can be measured. When the electrical work trader is registered in administrative divisions, the earth ohmeter is one of the necessary meters. Besides, the circuit meter (tester) and the megohmmeter are the lowest and necessary, too. |
Reason to use exchange for earth resistance measurement
Is the measurement of the ground resistance not direct current and why
measured by the exchange?It is because the generation of the battery with the
polarization action by electroanalysis and different kinds of earth poles
influences it in direct current.
That is, it becomes difficult to flow
gradually in the current even if a lot of currents flow first by a similar
thing's to electroanalysis of water and salt water happening by the moisture of
the soil, and generating the bubble of hydrogen, oxygen, and chlorine by the
electrode (polarization) if it measures it in direct current. With this, whether
when I may measure the current is not understood. Resistance changes. ,in a
word,
Moreover, an actual earth uses iron, uses the carbon, and is a board
of galvanizing though there might not be problem if the sheet copper this will
is used for an earth pole and a supplementary pole. If it is the different kind
of material, the battery is generated only with it. The current flows only with
the battery though direct current is not added in a word. It is a thing that it
depends in the direction of the direct current added by the measurement and the
current value is different. With this, the error margin is given to the
measurement of the ground resistance.
If it is an exchange, there is no
influence like the above-mentioned and an accurate measurement is possible.